Danfoss AK-SM 800A: Supermarket Refrigeration Controllers on KEV, and a New Flaw With No Patch Yet
CISA added three Danfoss AK-SM 800A flaws to its KEV catalog on 25 November, the day after an advisory on CVE-2026-129713, a new unauthenticated CVSS 9.8 stack overflow in the same controller line with no fix until version 5.5.x. These controllers run supermarket and cold-store refrigeration, and a European incident has already shown the cost.
Executive summary. The Danfoss AK-SM 800A series controls refrigeration in supermarkets and cold stores. On 25 November 2026 CISA added three older AK-SM 800A flaws to KEV based on active exploitation: CVE-2023-25914 (path traversal), CVE-2023-25915 (input validation, allowing remote command execution) and CVE-2025-41450 (improper authentication). A day earlier, CISA published an advisory on a new flaw, CVE-2026-129713: an unauthenticated stack-based buffer overflow in a CGI handler on AK-SM 8xxA controllers up to version 5.4.0, rated CVSS 9.8 (v3.1). Danfoss says a fix is coming in 5.5.x, with no date. Reports conflict on whether the new flaw is exploited; CISA reportedly says no public exploitation has been reported to it. Coverage links these devices to a European incident in which attackers locked refrigeration into defrost mode for hours, with reported food losses in the tens of millions. Until a patch exists, the defence is network design: get these controllers off the internet and behind segmentation and a VPN.
What it is
| Field | Detail |
|---|---|
| Product | Danfoss AK-SM 800A (AK-SM 8xxA) refrigeration system managers |
| Added to KEV (25 Nov) | CVE-2023-25914, CVE-2023-25915, CVE-2025-41450 |
| New flaw (24 Nov advisory) | CVE-2026-129713: unauthenticated stack overflow in a CGI handler |
| New flaw severity | CVSS 9.8 (v3.1) / 9.3 (v4) |
| Affected (new flaw) | 5.4.0 and earlier |
| Fix (new flaw) | Planned for 5.5.x, no date |
| Exploitation (new flaw) | Conflicting reports; treat as at risk |
The KEV CVE descriptions above come from tracker summaries; confirm each entry on CISA's catalog.
Why it needs industry attention
This is a physical-consequence problem, not a data one. A compromised system manager can change setpoints, force defrost cycles or stop refrigeration. The result is spoiled stock, food-safety exposure and, for pharmaceuticals, temperature-excursion losses. The devices are often installed by refrigeration contractors, connected for remote service, and then forgotten by IT. Security researchers (Claroty's Team82 among them) flagged AK-SM 800A weaknesses earlier this year. The KEV listing confirms that attackers are using the old flaws; the new one has no patch.
What to do
- Find every AK-SM 800A you own or that a contractor runs for you, including remote-service connections.
- Remove internet exposure. Put controllers behind a firewall, allow access only through a VPN, and never expose the web interface publicly.
- Segment OT from corporate IT and from guest or point-of-sale networks.
- Patch the KEV-listed flaws to Danfoss's current fixed firmware, and apply 5.5.x for CVE-2026-129713 as soon as it ships.
- Change default and shared credentials, and restrict contractor access to named, time-limited accounts.
- Plan for failure: independent temperature alarms and a manual fallback procedure, so a controller compromise doesn't go unnoticed overnight.
How to detect it
- Unexpected setpoint changes, defrost cycles or alarms outside normal schedules, and configuration changes with no matching work order.
- Web requests to the controller from outside the management network, especially malformed requests to CGI endpoints or path-traversal patterns (
../). - New or unknown remote-access sessions, and logins at unusual times.
- Controller reboots or crashes, which can indicate memory-corruption attempts against the unpatched flaw.
Conclusion
Old flaws are being exploited and a new one has no fix, on devices whose failure spoils food. Treat AK-SM 800A like any other OT system: off the internet, segmented, reached only by VPN, and watched for changes. Then patch as soon as Danfoss ships 5.5.x.
Do this now: inventory AK-SM 800A controllers (including contractor-managed), remove internet exposure, enforce VPN-only access, patch the KEV-listed flaws, and alert on setpoint and defrost changes.
Related: our state of exploitation report and the Learn track on network pentesting.
Sources: CISA KEV alert, 25 Nov, Facilities Dive, ZeroHour on CVE-2023-25915, ZeroHour on CVE-2025-41450, MLQ on CVE-2026-129713. Exploitation of the new flaw and loss figures vary by source; CISA's advisory is authoritative.
Related research
KEV and Critical CVE Tracker, 26 November 2026: What to Patch First, by Industry, With CVSS Vectors
CISA added 13 exploited vulnerabilities to KEV on 24 and 25 November, led by a CVSS 10.0 in Mitel MiCollab, with federal deadlines on 27 and 28 November. Add a second vCenter authentication bypass with a validated public exploit. Here is every critical item grouped by industry, with its CVSS vector, status, fix and a patch-first order.
Mitel MiCollab CVE-2026-133323: A CVSS 10 Command Injection in the Conferencing Server, Exploited and With a Public PoC
On 25 November CISA added five actively exploited Mitel MiCollab flaws to its KEV catalog. The headline is CVE-2026-133323, an unauthenticated blind command injection in the Audio, Web and Video Conferencing component, rated CVSS 10.0 by Mitel, with a public proof of concept. Federal agencies must fix it by 28 November.
Juniper Session Smart Conductor CVE-2026-103406: Root Command Injection on the Box That Runs Your SD-WAN
CISA added CVE-2026-103406 to its KEV catalog on 25 November. The flaw is a CVSS 9.8 OS command injection in the AutomatedProvisioner component of HPE Juniper Session Smart Conductor: a crafted salt minion ID runs commands as root. Juniper fixed it on 28 October; there is no workaround. Upgrade to 7.0.5, 7.1.7 or 7.2.3 or later.